To start, take a look at the ideas in the list below and VOTE for your favorite ideas submitted by other users. POST your own idea if it hasn’t been suggested yet. Include COMMENTS and share relevant business case details that will help our product team get more information on the suggestion. Please note that your ideas and comments are visible to all other users.


This page is for feedback specifically for AVEVA PI System. For links to our other feedback portals, please see the tab RESOURCES below.

ADD A NEW IDEA

Clear

Ideas

Showing 33 of 5192

trend log objects (BACnet object type 20) available from the connector

BACnet trendlog object present the opportunity to buffer at the edge where the data is collected and to gracefully recover from comms outages if data collection has been impacted. I would suspect the trendlog object could be handled similarly to ...
Guest over 3 years ago in PI Connectors / PI Connector for BACnet 0 No status

Allow EdgeCmd to set null or empty string parameter values

As per KB000042993, setting parameters with EdgeCmd that are <null> or "" (empty string) is not possible. Instead the JSON configuration file must be created and used in place. It would be more intuitive if executing commands such as: edgecm...
Mike Horrocks over 1 year ago in Edge Data Store / General 1 No status

Provide GUI for Configuration

Edge Data Store would require a GUI for configuration and health status to work more efficiently to set it up with too many efforts. The GUI should allow to set up the connection to the Data sources of the included PI Adapters, provide OPC UA brow...
Guest almost 2 years ago in Edge Data Store / General 0 No status

Make the connector a BACnet Device (get a BTL listing)

Some devices can only send COV notifications to other BACnet devices. Since the Connector is not a device and does not respond to who-is messages (and does not listen on port 47808), the connector is unable to utilize COV subscriptions for these d...
Paul Kim over 3 years ago in PI Connectors / PI Connector for BACnet 0 No status

Suppress the creation of "Status Flag" PI Points

The end-user would like to suppress the creation of the "Status Flag" PI Points, as they wish to keep their point count to a minimum due to the license-enforced point limit.
Guest over 3 years ago in PI Connectors / PI Connector for BACnet 0 No status

EDS: OPC DA Connector

Ability for OPC DA connector to write data to Edge Data Store.
Guest over 3 years ago in Edge Data Store / Ingress 1 Declined

Program objects (BACnet object type 16) also bought through by the connector

The program object description is often very useful to understand what the various object instances relate to. At our site the description holds the Asset designation and that would allow correct assignment of the analogue and binary object instan...
Guest over 3 years ago in PI Connectors / PI Connector for BACnet 0 No status

Conditional Data Egress for Edge Data Store

Scenario: In a remote monitoring scenario, Edge Data Store is collecting data through OPC UA or ModbusTCP with a certain sampling rate (assumingly 1s). For normal operations, EDS shall egress only an aggregated one minute value of all analogue str...
Guest almost 2 years ago in Edge Data Store / Egress 0 No status

Log device information when the Connector receives errors from a device

Currently the Connector logs when it receives errors, but does not print information that can be used to determine which device is reporting the errors. We currently need to perform a wireshark trace to look at the individual packets to determine...
Guest over 3 years ago in PI Connectors / PI Connector for BACnet 0 No status

Distribute-Broadcast-To-Network broadcast for Discovery Tool and Connector

When running the discovery tool from a subnet with no BBMD to query BACnet devices on a separate subnet, it seems like the auto discovery tool is seen as a ‘foreign device’, so the devices do not respond correctly. When analyzing a Wireshark trac...
Guest over 3 years ago in PI Connectors / PI Connector for BACnet 0 No status