Skip to Main Content
AVEVA™ PI System™ Feedback Portal

Welcome to our feedback site!


We created this site to hear your enhancement ideas, suggestions and feedback about AVEVA products and services. All of the feedback you share here is monitored and reviewed by the AVEVA product managers.

To start, take a look at the ideas in the list below and VOTE for your favorite ideas submitted by other users. POST your own idea if it hasn’t been suggested yet. Include COMMENTS and share relevant business case details that will help our product team get more information on the suggestion. Please note that your ideas and comments are visible to all other users.


This page is for feedback specifically for AVEVA PI System. For links to our other feedback portals, please see the tab RESOURCES below.

Status No status
Product PI Connectors
Created by Guest
Created on Aug 20, 2022

IEC 60870-5-104: Interrogation Period

Currently, the PI Connector for IEC 60870-5-104's Interrogation Period (for each data source) can only go as low as 1 hour. As a PI System Administrator, I'd like to be able to set this value lower (on the order of seconds) so that all PI Points are updated frequently, even if the data source isn't sending unsolicited updates.
  • Attach files
  • Gabriel Verreault
    Reply
    |
    Aug 20, 2022
    The proper approach would be to change the Cause of Transmission (CoT) of the item to periodic/cyclic if you want a constant (cyclic) scan of the data. General interrogation should not be used for this purpose.