To start, take a look at the ideas in the list below and VOTE for your favorite ideas submitted by other users. POST your own idea if it hasn’t been suggested yet. Include COMMENTS and share relevant business case details that will help our product team get more information on the suggestion. Please note that your ideas and comments are visible to all other users.


This page is for feedback specifically for AVEVA PI System. For links to our other feedback portals, please see the tab RESOURCES below.

Status No Status
Product PI Connectors
Created by Guest
Created on Aug 20, 2022

Setting of parameters k and w for IEC 60870-5-104

Parameters k (Maximum number of outstanding I format APDUs) and w, cannot be adjusted, while vendors recommend customers to set it to k=12 and w=8
  • Attach files
  • Gabriel Verreault
    Reply
    |
    Aug 20, 2022
    For clarification: K: Maximum unacknowledged transmitted APDUs. The master does not send more APDUs if the maximum number of ADPUs have been transmitted and have not been acknowledged. W: Maximum unacknowledged received APDUs. This setting works in conjunction with T2 to limit how often the master acknowledges APDUs. Increasing this setting can reduce bandwidth required for acknowledging