Skip to Main Content
AVEVA™ PI System™ Feedback Portal

Welcome to our feedback site!


We created this site to hear your enhancement ideas, suggestions and feedback about AVEVA products and services. All of the feedback you share here is monitored and reviewed by the AVEVA product managers.

To start, take a look at the ideas in the list below and VOTE for your favorite ideas submitted by other users. POST your own idea if it hasn’t been suggested yet. Include COMMENTS and share relevant business case details that will help our product team get more information on the suggestion. Please note that your ideas and comments are visible to all other users.


This page is for feedback specifically for AVEVA PI System. For links to our other feedback portals, please see the tab RESOURCES below.

Status No status
Product PI Connectors
Created by Ee Sheing Lee
Created on Nov 19, 2025

OPC UA server failover based on watchdog tag

Gen2 PI Connector for OPC UA support OPC UA server level failover.

How the Connector determine when to failover to the other OPC UA server:

  1. As per 6.6.2.4.2 ServiceLevel , this is used by the client to determine whether to connect/disconnect from the OPC UA server

  2. As per Failover and redundancy , the connector will fail back to a redundant OPC UA server provided the indicator (ServiceLevel) of a current server is within the interval <2-200> and the specified time expired.

This enhancement request is to have another option to failover based on a watchdog tag instead of using the OPC UA Server ServiceLevel.
Example, PI Interface for OPC DA has this similar feature as per Configure a single watchdog PI point

  • Attach files