To start, take a look at the ideas in the list below and VOTE for your favorite ideas submitted by other users. POST your own idea if it hasn’t been suggested yet. Include COMMENTS and share relevant business case details that will help our product team get more information on the suggestion. Please note that your ideas and comments are visible to all other users.


This page is for feedback specifically for AVEVA PI System. For links to our other feedback portals, please see the tab RESOURCES below.

Status Completed
Categories Symbols
Created by Guest
Created on Aug 18, 2022

Use AF attribute traits to set symbol scale or limits

As a PI Vision user, I would like to have the option to set the scale or limits of any symbol based on the attribute traits defined in AF. When the symbol contains multiple attributes, it would be useful to be able to select only one attribute to define the scale of the symbol.
  • ADMIN RESPONSE
    Aug 18, 2022
    PI Vision currently supports this functionality. When the ‘database’ option is selected for a symbol scale, if the attribute has Min and Max traits, the traits will automatically be used to define the scale on the PI Vision symbol.
  • Attach files
  • Nenad Kovacevic
    Reply
    |
    Aug 18, 2022
    This seems obvious. I hope it gets implemented, and soon.
  • Guest
    Reply
    |
    Aug 18, 2022
    PI Vision currently supports this functionality. When the 'database' option is selected for a symbol scale, if the attribute has Min and Max traits, the traits will automatically be used to define the scale on the PI Vision symbol.
  • Jason Gogal
    Reply
    |
    Aug 18, 2022
    Dynamic would be better. And by min and max traits, does that mean Minimum and Maximum limits?
  • Jason Gogal
    Reply
    |
    Aug 18, 2022
    Symbols such as bar gauge default 0-100 for scale limits. It would be nice if they were dynamic by default.
  • Guest
    Reply
    |
    Aug 18, 2022
    Hi Jason, Yes, you are right. By min and max traits, it means Minimum and Maximum limits which are configured in AF. When an attribute's min and max traits are configured to be dynamic, which is supported in AF, its scale in PI Vision will also be dynamic by default (scale range uses database settings by default). Thanks for your feedback. Should you need help configuring dynamic AF traits, please contact OSIsoft Tech Support. Best, Victor Zhang Technical Product Manager, Visualization | OSIsoft