Skip to Main Content
AVEVA™ PI System™ Feedback Portal

Welcome to our feedback site!


We created this site to hear your enhancement ideas, suggestions and feedback about AVEVA products and services. All of the feedback you share here is monitored and reviewed by the AVEVA product managers.

To start, take a look at the ideas in the list below and VOTE for your favorite ideas submitted by other users. POST your own idea if it hasn’t been suggested yet. Include COMMENTS and share relevant business case details that will help our product team get more information on the suggestion. Please note that your ideas and comments are visible to all other users.


This page is for feedback specifically for AVEVA PI System. For links to our other feedback portals, please see the tab RESOURCES below.

ADD A NEW IDEA

Clear

Ideas

Showing 48 of 5194

displayname/localname for identifier that excludes namespace and data type

Example: OPC UA Server 'Name': 2.0:W-HVAC-AC-1-IO!Wtot Namespace: 2 Datatype: 0 Identifier: W-HVAC-AC-1-IO!Wtot OPC UA Server 'DisplayName': W-HVAC-AC-1-IO!Wtot OPC UA Adapter {Identifier} returns: 2.0:W-HVAC-AC-1-IO!Wtot Required stream name: W-H...
Guest over 1 year ago in AVEVA™ Adapters / AVEVA Adapter for OPC UA 0 No status

Make the connector a BACnet Device (get a BTL listing)

Some devices can only send COV notifications to other BACnet devices. Since the Connector is not a device and does not respond to who-is messages (and does not listen on port 47808), the connector is unable to utilize COV subscriptions for these d...
Paul Kim over 3 years ago in PI Connectors / PI Connector for BACnet 0 No status

Suppress the creation of "Status Flag" PI Points

The end-user would like to suppress the creation of the "Status Flag" PI Points, as they wish to keep their point count to a minimum due to the license-enforced point limit.
Guest over 3 years ago in PI Connectors / PI Connector for BACnet 0 No status

Enable Adapter for OPC UA to use the Pub/Sub method

Pub/Sub is proposed to be a more efficient and scalable method of transferring data using OPC UA. Allowing the adapter to access data in this way would increase the options for data collection, and allow the OPC UA adapter to be used in many more ...
Mike Horrocks over 1 year ago in AVEVA™ Adapters / AVEVA Adapter for OPC UA 0 No status

PI Adapter for OPC UA should send the previous value when it has been with the same value for a long time

"This enhancement request proposes a solution to address the issue of data interpolation between two values far apart in time in adapter data collection. The suggestion is to include the value right before the new data point, ensuring the fidelity...
Fabio Dani over 2 years ago in AVEVA™ Adapters / AVEVA Adapter for OPC UA 1 No status

Program objects (BACnet object type 16) also bought through by the connector

The program object description is often very useful to understand what the various object instances relate to. At our site the description holds the Asset designation and that would allow correct assignment of the analogue and binary object instan...
Guest over 3 years ago in PI Connectors / PI Connector for BACnet 0 No status

Improve the message for performing on demand History Recovery on datacollectionmode: "CurrentWithBackfill" and "CurrentOnly"

Running edgecmd to perform HR on demand on the datasource: datacollectionmode of Non HistoryOnly. will return the following error: Operation Failed: NotFound (404)Unexpected error: Unexpected character encountered while parsing value: 0. path '", ...
Ee Sheing Lee over 1 year ago in AVEVA™ Adapters / AVEVA Adapter for OPC UA 0 No status

Log device information when the Connector receives errors from a device

Currently the Connector logs when it receives errors, but does not print information that can be used to determine which device is reporting the errors. We currently need to perform a wireshark trace to look at the individual packets to determine...
Guest over 3 years ago in PI Connectors / PI Connector for BACnet 0 No status

Distribute-Broadcast-To-Network broadcast for Discovery Tool and Connector

When running the discovery tool from a subnet with no BBMD to query BACnet devices on a separate subnet, it seems like the auto discovery tool is seen as a ‘foreign device’, so the devices do not respond correctly. When analyzing a Wireshark trac...
Guest over 3 years ago in PI Connectors / PI Connector for BACnet 0 No status

scaling/scale data selection(s)

Simplify data management, setting scale at source
Guest over 1 year ago in AVEVA™ Adapters / AVEVA Adapter for OPC UA 0 No status